Features:
Free Chlorine - Total Chlorine - Ph - ORP - Ozone - Hydrogen Peroxide - Chlorine Dioxide - Fluoride - Conductivity
Microprocessor controlled continuous analyzer with integrated Proportional Integral controller for water analysis applications. Our approved Potentiostatic Amperometric measuring principle is able to measure from low conductive- to salt water. No chemicals have to be added.
The controller part is equipped with three relays. Two for adjustable set points. One for general alarm (calibration error) and time delayed adjustable lower and upper limit.
The 0/4 - 20 ma. output can be used as a controlling (PI), or as a recording output. Temperature compensation is manual or automatic.
A two line illuminated alphanumerical display indicates the measured value, temperature, action of the set points, and customer programmed data.
All in and Outputs are isolated (no ground loops).